Application The meter is designed to measure three phase four wire AC active energy like residential , utility and industrial application. It is a long life meter with the advantage of high stability , high over load capability , low power loss and small volume . Prouducts character 1. max current:80A DC. 2. Standard 7-modulus width,TH35-7.5 type rail installation 3. Multi-function parameter measurement, providing voltage, current, active power, reactive power, apparent power, power factor, phase Angle, etc 4. Support two-way electric energy metering, provide monthly electricity consumption statistics for the last 12 months, and daily electricity consumption statistics for the last 31days 5. In-built relay, support remote control and prepaid management control,providing latest 50 times opertation records,10 SOE event records 6. Support the power consumption parameter monitoring and alarm function 7. Support WIFI,LoRa,NB-IoT,4G etc. wireless communication way 8. Support 1 pulse output, 1 RS485 communication
Product Description
Model NO.
|
Dac7321c
|
Theory
|
Electronic Meter
|
Power Meter Connection
|
Feed-through Type
|
Measured Signal
|
Pulse Peak
|
Type
|
Power Meter
|
Certification
|
RoHS, ISO, CE
|
Customized
|
Customized
|
Model No.
|
Dac7321c
|
Related Voltage
|
3*110/190V or 230/400V AC
|
Rate Current(Ib)
|
5A
|
Communication
|
Modbus
|
Connect
|
AC
|
Measure Type
|
1p2w
|
Pulse Constant
|
1000 Imp/Kwh
|
Operating Temperature
|
-25 to +55ºC
|
Harmonics Emissions
|
IEC 61000-3-2
|
IP Degree of Protection
|
Designed to IP51 Front Display, IP30 Meter Body
|
Pulse Width
|
60/100/200 Milliseconds (Configurable)
|
Transport Package
|
Paper Carton+Pallets
|
Specification
|
98*126*80 mm
|
Trademark
|
XOCA
|
Origin
|
Zhejiang China
|
HS Code
|
903033900
|
Production Capacity
|
1000000 PCS /Year
|
Technicial parameters
Model |
DAC7300C/DAC7301C/DAC7321C/DAC7320C |
Electrical Characteristics |
Rate voltage (Un) |
3*110/190V or 230/400V AC |
Operational voltage |
L-N: 85 to 275V AC; L-L: 85 to 480V AC |
Overload capacity of voltage |
2*Un for 1 second |
Rate current(Ib) |
5A |
Maximum current(Imax) |
80A |
Operational current |
0.1%Ib to Imax |
Overload capacity of current |
30*Imax for 0.01 second |
Operational frequency range |
45 - 65Hz |
Power consumption |
<2W/10VA |
Pulse constant |
1000 imp/kWh |
Display |
LCD with backlight |
Maximum reading of energy |
999999.99 kWh/kVarh |
Measure type |
Three phase four wire |
Measurement accuracy |
Voltage, Current |
±0.5% |
Active power |
±1.0% or 0.5% |
Reactive power |
±2.0% |
Apparent power |
±1.0% |
Active energy |
±1.0% or 0.5% |
Reactive energy |
±2.0% |
Power factor |
±1.0% |
Frequency |
±0.2% |
Environmental Characteristics |
Operating Temperature |
-25 to +55ºC |
Storage Temperature |
-40 to +80ºC |
Humidity |
< 90%, non-condensing |
Pollution Degree |
2 |
Altitude |
Up to 2000m |
Vibration |
10 Hz to 150Hz, IEC 60068-2-6 |
IP Degree of Protection |
Designed to IP51 front display, IP30 meter body |
Electromagnetic Characteristics |
Electrostatic Discharge |
±8kV(contact discharge),±15kV(air discharge); Level 4, according IEC 61000-4-2 |
Immunity to Radiated Fields |
10V/m,80 - 2000MHz; Level 3, according IEC 61000-4-3 |
Immunity to Electrical Fast Transients |
±4kV; Level 4, according IEC 61000-4-4 |
Immunity to Surges |
±4kV; Level 4, according IEC 61000-4-5 |
Immunity to Conducted Disturbances |
10V,0.15 - 80MHz; Level 3, according IEC 61000-4-6 |
Immunity to Magnetic Fields |
IEC 61000-4-8 |
Immunity to Voltage Dips |
IEC 61000-4-11 |
Radiated Emissions |
Class B, according EN55011 |
Conducted Emissions |
Class B, according EN55011 |
Harmonics Emissions |
IEC 61000-3-2 |
Safety |
Overvoltage Category |
CAT III, according IEC 61010-1 |
Measurement Category |
CAT III, according IEC 61010-1 |
Insulation |
AC Voltage Test: 4kV for 1 minute |
Impulse Voltage Test: 6kV - 1.2/50µS waveform |
Protective Class |
II, according IEC61010-1 |
Communications |
Interfaces standard and protocols |
2-wire RS485, Modbus RTU Optional: Mbus |
Buad rate |
1200 to 9600 bps, default is 9600 bps |
Parity bit |
None, Even, Odd, default is None |
Stop bit |
1 or 2, default is 1 |
Response time |
<100ms |
Transmission mode |
half-duplex |
Transmission distance |
Up to 1000m |
Max. Bus loading |
32 pcs |
Wireless communications |
Types that can be supported |
WIFI, LoRa, NB-IoT, 4G |
Pulse output |
Interface type |
Open collector optocoupler |
Pulse constant |
Per pulse equal 0.001/0.01/0.1/1 kWh/kvarh (Configurable) |
Pulse width |
60/100/200 milliseconds (Configurable), default is 100milliseconds |
Pulse output type |
Import/export/total active energy, Import/export/total reactive energy (Configurable) |
Class |
Class A, according IEC 62053-31 |
Input voltage |
5 to 27 VDC |
Product description
A
DIN Rail WiFi Prepaid Electric Energy Meter is an advanced electricity meter designed to accurately measure and monitor electrical energy consumption in industrial and commercial settings. The product parameters you provided are as follows:
Related Voltage:
This energy meter is compatible with two different voltage configurations:
3-phase: 110/190V AC
3-phase: 230/400V AC
Rate Current (Ib):
The rate current, or Ib, is 5A. This means the meter is designed to handle a maximum current of 5 amperes in the circuit it is monitoring.
Communication:
The energy meter utilizes Modbus communication protocol, which allows for data transmission and remote monitoring of energy consumption.
Connect:
This energy meter connects to an AC (alternating current) power source, making it suitable for use in AC electrical systems.
Measure Type:
The meter operates in a 1-phase 2-wire (1p2w) measurement configuration, which is commonly used in single-phase electrical systems.
Pulse Constant:
The meter has a pulse constant of 1000 Imp/KWh. This parameter defines the number of pulses generated by the meter for every kilowatt-hour (KWh) of electrical energy consumed. This is useful for recording energy consumption accurately.
Operating Temperature:
The energy meter is designed to operate within a temperature range of -25 to +55 degrees Celsius (-25°C to +55°C). This wide operating temperature range ensures that the meter can function reliably in various environmental conditions.
Harmonics Emissions:
The meter complies with the IEC 61000-3-2 standard for harmonics emissions. This means it meets the requirements for limiting harmonic distortion in the electrical system, ensuring that the meter does not introduce interference or distortion in the power supply.
Overall, this DIN Rail WiFi Prepaid Electric Energy Meter is a versatile and reliable device for monitoring energy consumption in 3-phase electrical systems. It offers accurate measurement, remote communication capabilities via Modbus, and is suitable for use in various industrial and commercial applications while adhering to international standards for harmonics emissions.